40 Important Product Information
GFK-1671P
Open Issues and Problems
Import of LM90 or Control Folder Issues
ID Description
CR71941/
CR71940/
CR71976
Control Version 2.20 VersaMax Configurations can’t be imported into VersaPro.
Details: Control Version 2.20 VersaMax folders can’t be imported into VersaPro.
Resolution: Control VersaMax folders should first be opened with Control Release 2.3 and
then saved. The updated folder can then be imported into VersaPro.
CR73144
Invalid Program after import and modification of Series 90 Micro LM90 folder.
Details: A Logicmaster 90 Micro program that contains a vertical wire immediately in front of
a single coil will result in the error 0x05F2 - Invalid Program (or too large for PLC) if it is
imported into VersaPro, edited, and then stored to the Series 90 Micro PLC. The Series 90
Micro does not support the optimization that VersaPro performs on this structure.
Example 4
Resolution: The work around is to add an ALW_ON contact in front of any single coil that
has a vertical wire immediately in front of it.