Important Product Information 23
GFK-1671P
Problems Resolved by Version 2.02
Hardware issues resolved:
17581
GSD file import error
Details: When importing a GSD file into HE693PBM100 or HE693PBM101 module, the
import will result in an error message 'Unexpected value' if a semi-colon is present at the end
of 'Ident_Number' line.
Resolution: Import works correctly in VersaPro 2.02 and no error messages are displayed
19888
Unused Slave Information and Data Areas printed in HWC report
Details: Slave Information and Data Areas that are not used are also included in the HWC
Report printout.
Resolution: Only the used Slave Information and Data Areas will be printed in VersaPro 2.02.
21359
LM90 folder with CMM311 configuration imports incorrectly in VersaPro
Details: When a CMM311 folder with configuration mode set to CCM/SNP is imported, the
configuration mode changes to SNP/CMM in VersaPro. A similar behavior is observed with
RTU/CCM and RT/SNP modes.
Resolution: All modes import correctly in VersaPro 2.02
21688
Invalid SNP ID gets cleared in parameter editor
Details: When you set the SNP ID to an invalid value (e.g. "AB C") it will cause an error in the
module but when you open and close the editor, the parameter shows as empty.
Resolution: The invalid value is now displayed in red in the parameter editor.
21251
Storing a ALG430 configuration results in a system configuration mismatch
Details: When a configuration with VersaMax ALG430 module is stored to PLC, a system
config mismatch on the ALG430 modules is obtained.
Resolution: The configuration is correctly stored without any problems.
22275
Produced Exchange Period if set to less than 10 gets resets to default value 200 after
reopening
Details: In VersaPro 2.01, set the Produced Exchange Period to a value less than 10 in
Ethernet NIU module. Save, Close and Reopen the configuration file. The parameter is reset to
the default value of 200.
Resolution: The parameter value is retained on reopen in VersaPro 2.02.
22166
Reference Addresses still allocated when a GBC Redundant modules are added using
Redundancy Wizard in a slot with a I/O module
Details:
1) Add an I/O module to slot 2 in a 90-70 system and open the editor
1) Run the Red Wizard on a 90-70 system.
2) Choose Add GBC for redundancy
3) Select Rack 0 and Slot 2 -> for location
4) Finish
The I/O module's parameter editor is still open and its reference addresses are still allocated to
the rack system in the Reference View.
Resolution: On adding Redundancy scheme, the I/O module’s parameter editor is closed and
its reference addresses are cleared in VersaPro 2.02.
Communication issues resolved:
ID Description
20762
HDRVSNP.exe locks up when trying to dial into a line that is busy over a modem
connection.
Details: Configure VP for a modem connection and dial into a line that is busy.
HDRVSNP.exe locks u
and the onl
wa
to recover is to use the task mana
er to kill the