36 Important Product Information
GFK-1671P
Open Issues and Problems
ID Description
Insert of CAM blocks from other folders, Drag and Drop, Cut/Copy/Paste of CAM
blocks between Multiple instances of VersaPro is not supported.
Details: If you attempt to insert CAM blocks from another folder or drag and drop,
cut/copy/paste CAM blocks from other instances of VersaPro, the operation may be successful
but the CAM profiles will not be copied to the new folder.
Resolution: You should use the import features within the CAM editor in order to re-use
blocks between folders. Also, within VersaPro, you can copy a CAM block by having only
one instance of VersaPro open, copy a CAM block, close the folder, open a new folder and
then paste the block into the new folder.
Motion program store error when storing Motion zip file of size greater than 32k to PLC
with old 9030 firmware using VersaPro 2.0x.
Details: The maximum size allowed for the DSM Motion Zip files is increased to 64k from
32k in VersaPro 2.02. If you store attempt to store a Motion zip file of size greater than 32k to
a 9030 PLC with the older revision of the firmware, you will get a Store error “0x0400 –
Unknown TargetComm Error”.
Resolution: This is because the older revision of 9030 firmware supports a Motion zip file
with a maximum size of 32k only. You will need to upgrade to the new revision 10.60 in order
to store Motion zip file of size greater than 32k.
Fault Table Issues
ID Description
CR75877/
CR75906
Fault Table: Can not bring up Fault table when connected to 9070 CPU780.
Details: After connecting to a 90-70 CPU780 or CPU771 with the main VersaPro application,
if you try to bring up the fault table using “Tools®Fault Table” menu, an error message
“Maximum number of users exceeded for Requested Port.”
Resolution: This CPU does not support multiple connections so both the VersaPro main
application and the Fault Table cannot be connected at the same time. You should disconnect
VersaPro from the PLC and then launch the Fault Table. When you need to reconnect to the
PLC with VersaPro, you should first close the Fault Table.
Find and Replace Issues
ID Description
CR72914
Find/Replace Auto-Assign Increments by 16 on contacts/coils.
Details: Using the Find/Replace dialog, I specified to replace %S00008 with %T. Each time
the replace occurred on a contact, the Auto-Assign created a new Word type variable. You
would expect it to create a new Bit type variable since a Bit type memory is specified for the
replace. This issue also applies to IL Blocks and Boolean Constructs (I.e. LD_BOOL,
ST_BOOL,...)
Resolution: You should avoid using the auto-assign feature when using find/replace since the
assignments will not be optimal and the type created for the replacement may not be correct.
To avoid using the auto-assign feature, you must specifically put a reference address in for the
replace. For example %T2 in the case described.